EasyManua.ls Logo

IBC DC Series - Hot Water Does Not Reach Temperature

IBC DC Series
82 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
INSTALLATION AND OPERATION INSTRUCTIONS
5-10
DC SERIES BOILERS / WATER HEATERS DC 15-95, DC 15-96, DC 20-125, DC 33-160
5.4.8 Hot Water Does Not Reach Temperature
POSSIBLE CAUSES SOLUTION
DHW ow too high. Adjust the inlet assembly, insert a ow restrictor.
Temperature setting for water circuit too low. Adjust the hot water circuit, depending on the desired temperature and
system conguration. See Table of Programmable Parameters in DC/HC
Controller Manual.
Water temperatures are set incorrectly Target water temperature is set higher than the maximum water
temperature.
No heat transfer as a result of lime scale or
fouling in the heat exchanger DHW side.
Descale or ush the exchanger DHW side.
Cold water temperature <5°C.