The equipment is suitable for installation in the following:
v Network telecommunications facilities
v Locations where the NEC (National Electrical Code) applies
The intrabuilding ports of this equipment are suitable for connection to intrabuilding or unexposed
wiring or cabling only. The intrabuilding ports of this equipment must not be metallically connected to the
interfaces that connect to the OSP (outside plant) or its wiring. These interfaces are designed for use as
intrabuilding interfaces only (Type 2 or Type 4 ports as described in GR-1089-CORE) and require isolation
from the exposed OSP cabling. The addition of primary protectors is not sufficient protection to connect
these interfaces metallically to OSP wiring.
Note: All Ethernet cables must be shielded and grounded at both ends.
The ac-powered system does not require the use of an external surge protection device (SPD).
The dc-powered system employs an isolated DC return (DC-I) design. The DC battery return terminal
shall not be connected to the chassis or frame ground.
The dc-powered system is intended to be installed in a common bonding network (CBN) as described in
GR-1089-CORE.
Safety notices xiii

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the IBM Power Systems 7063-CR1 and is the answer not in the manual?

IBM Power Systems 7063-CR1 Specifications

General IconGeneral
Model7063-CR1
TypeServer
Operating SystemAIX, IBM i, Linux
RAID Levels0, 1, 5, 6, 10
Memory Slots16
StorageSAS
Processor Cores4 per processor
Disk Bays8
Power SupplyRedundant
Form FactorRack-mountable