Appendix D: Modbus Application Notes
ET-7000 AIO User Manual, Apr. 2009, V1.04, EMH-011-104----------130
Detailed Modbus Address Table for ET-7015
(0xxxx) DO address
Begin address Points Description
Registers
per Point
Range
Access
Type
595 7 Enable/Disable AI channel 1
0=disable
1=enable
(Default=1)
R/W/E
629 1 50/60Hz rejection for AI 1
0=50Hz
1=60Hz
(Default=1)
R/W/E
631 1 AI data format 1
1=engineering
0=hex
(Default=0)
R/W/E
632 1 Return the factory calibration (All) 1 1=clear R/W/E
830 1 Enable/ Disable calibration(All) 1
0=disable
1=enable
R/W
831 1 Zero calibration command of ch0 1 1=run (pulse) R/W
832 1 Span calibration command of ch0 1 1=run (pulse) R/W
833 1 Zero calibration command of ch1 1 1=run (pulse) R/W
834 1 Span calibration command of ch1 1 1=run (pulse) R/W
835 1 Zero calibration command of ch2 1 1=run (pulse) R/W
836 1 Span calibration command of ch2 1 1=run (pulse) R/W
837 1 Zero calibration command of ch3 1 1=run (pulse) R/W
838 1 Span calibration command of ch3 1 1=run (pulse) R/W
839 1 Zero calibration command of ch4 1 1=run (pulse) R/W
840 1 Span calibration command of ch4 1 1=run (pulse) R/W
841 1 Zero calibration command of ch5 1 1=run (pulse) R/W
842 1 Span calibration command of ch5 1 1=run (pulse) R/W
843 1 Zero calibration command of ch6 1 1=run (pulse) R/W
844 1 Span calibration command of ch6 1 1=run (pulse) R/W
(3xxxx) AI address
Begin address Points Description
Registers
per Point
Range
Access
Type
0 7 Analog Input word -32768 ~ +32767 R