Chapter 3 Web Configuration Page
,
ET-7000 AIO User Manual, Apr. 2009, V1.04, EMH-011-104----------80
Signed 32
A 32-bit value with sign. The Most significant word (register) is on
the low address.
Unsigned 32 (swapped)
A 32-bit positive value. The Most significant word (register) is on
the high address.
Signed 32 (swapped)
A 32-bit value with sign. The Most significant word (register) is on
the high address.
Float
A 32-bit floating point. (IEEE754). The Most significant word
(register) is on low address.
Float (swapped)
A 32-bit floating point. (IEEE754). The Most significant word
(register) is on high address.
Click the button to save all settings.
The diagram below shows an example of how to select a Coil register type with a Modbus
Register Address of 1 and Alias name of Voltage 1.
Other text fields that aren’t related to the Coil register type will be disabled.
The Modbus Register and Alias text fields are only related to the Coil and Discrete Input
register types, but the other fields aren’t related.