Tiny Modbus/TCP to RTU/ASCII Gateway
Copyright © 2020 ICP DAS CO., Ltd. All Rights Reserved. - 101 -
Defined Exception Codes for tGW-700/GW-2200:
Code
Name and Description
0x0B
GAT EWAY TARGET DEVICE FAILED TO RESPOND
Timeout. The slave device does not respond within the timeout value, the tGW-700/GW-2200 will return this
code.
0x4B
GAT EWAY TARGET DATA FAILED TO RESPOND
Timeout. The slave device is still sending data when timed out, the tGW-700/GW-2200 will return this code.
Please use larger Slave Timeout value for the serial port of the tGW-700/GW-2200 module.
0x41
MODBUS PROTOCOL FORMAT ERROR
The tGW-700/GW-2200 will return this code when slave response is invalid Modbus message.
0x42
WRONG DATA LENGTH
The tGW-700/GW-2200 will return this code when tGW-700/GW-2200 received wrong data length.
Please use larger Slave Timeout value for the serial port of the tGW-700/GW-2200 module.
0x43
CRC ERROR
The tGW-700/GW-2200 will return this code when the CRC of the slave response is wrong.