EasyManua.ls Logo

ICP DAS USA tGw-735 - 4.5 Self-Test

Default Icon
109 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Tiny Modbus/TCP to RTU/ASCII Gateway
Copyright © 2020 ICP DAS CO., Ltd. All Rights Reserved. - 49 -
7. Click “Submit” to save your settings.
4.5 Self-Test
1. Download and install the Modbus Poll test program at below link.
https://www.modbustools.com/download.html
2. Double-click the Modbus Poll shortcut to open.
3. Select the Read/Write Definition…” item from the Setup menu to open the
Read/Write Definition dialog box.
4. Configure the settings for the Slave.
Note: The Modbus Slave settings depends on your Modbus device.
5. Select the Connect…” item from the Connection menu to open the Connection
Setup dialog box.

Table of Contents

Related product manuals