TYPICAL CONDENSATE SYSTEM
CONDENSATE PUMPS
The condensate pump is designed to collect and remove condensate and can be used
with high eciency condensing boilers.
TECHNICAL INFORMATION
Maximum flow rate 440 litres/hour
Electrical supply 230V AC / 50-60 Hz 0.8amps
Alarm contact NC 4 Amps resistive
Overheat protection 130˚C
Tank Capacity 2.0 Litres
Maximum vertical head 4.5m
Maximum horizontal length 30m
IDEAL COMMERCIAL BOILERS - CONDENSATE PUMP COMPATIBILITY
BOILER COMPATIBLE
EVOMAX 2 - 30 - 150kW
IMAX XTRA - 80 - 280kW
IMAX XTRA EL - 320 - 1240kW
EVOMOD - 250 - 1000kW
EVOJET - 150 - 1450kW
TERMINATION TO DRAIN / GULLEY