40
TYPICAL CONDENSATE SYSTEM
CONDENSATE PUMPS
The condensate pump is designed to collect and remove condensate and can be used
with high eciency condensing boilers.
TECHNICAL INFORMATION
Maximum flow rate 440 litres/hour
Electrical supply 230V AC / 50-60 Hz 0.8amps
Alarm contact NC 4 Amps resistive
Overheat protection 130˚C
Tank Capacity 2.0 Litres
Maximum vertical head 4.5m
Maximum horizontal length 30m
IDEAL COMMERCIAL BOILERS - CONDENSATE PUMP COMPATIBILITY
BOILER COMPATIBLE
EVOMAX 2 - 30 - 150kW
IMAX XTRA - 80 - 280kW
IMAX XTRA EL - 320 - 1240kW
EVOMOD - 250 - 1000kW
EVOJET - 150 - 1450kW
TERMINATION TO DRAIN / GULLEY
SEE INSTALLATION MANUAL FOR FULL
INSTRUCTIONS AND SYSTEM OPTIONS
TYPICAL CONDENSATE SYSTEM