5
CHAPTER 1
CHAPTER 1 - PRE-INSTALLATION REQUIREMENTS
1.5.3 Flex Polypropylene Vent System Restrictions
2 [60 mm] Flex polypropylene venting is limited up
to the EXALT Solo 110.
Contact approved polypropylene vent
manufacturer for a copy of their installation
instructions. Read, understand and follow all
of the vent manufacturer’s instructions before
beginning the installation. Contact vent
manufacturer if you require any technical
support.
Failure to properly install and support vent
system can cause the venting system to fail,
resulting in substantial property damage,
serious injury, or death.
Approved for vertical installations only, where a
clean, structurally sound unused chimney or chase
is used as a raceway.
Vertical osets must not exceed 45° and are limited
to a maximum number of 2.
Requires rigid polypropylene vent pipe with
approved locking band clamps or connector
rings and wall straps or support clamps from the
appliance to the entrance of the chimney or chase.
Maintain 5/8” [1.6 cm] per foot slope back
toward appliance on all horizontal runs of rigid
polypropylene vent pipe.
The use of a wall plate is required to seal rigid
polypropylene vent pipe at the entrance of the
chimney or chase to prevent mortar or cement
from contacting the polypropylene vent pipe.
Requires supports (elbow or base, ex chimney
and bracket), spacers, chimney cap and end pipe.
Consult vent manufacturer for complete list of
required parts.
Any termination piping external to the building
must be UV resistant.
Do not apply insulation directly to vent. Maintain
vent manufacturers clearances to combustibles.
Flex plastic venting systems shall not pass through
rated re separations.
Prior to assembly of any joints, ensure joint gasket
is present and properly installed. Contact vent
manufacturer if gasket is missing or damaged. Verify
the integrity of joints upon completion of the vent
system.
WARNING
1.5.2 Rigid Polypropylene Vent System Restrictions
Contact approved polypropylene vent
manufacturer for a copy of their installation
instructions. Read, understand and follow all
of the vent manufacturer’s instructions before
beginning the installation. Contact vent
manufacturer if you require any technical
support.
Failure to properly install and support vent
system can cause the venting system to fail,
resulting in substantial property damage,
serious injury, or death.
Rigid polypropylene vent pipe must be installed
with approved locking band clamps or connector
rings and supports (wall strap or clamp, elbow or
base, etc.). Consult vent manufacturer for com-
plete list of required parts.
Maintain 5/8” [1.6 cm] per foot slope back toward
appliance on all horizontal runs.
The use of a wall plate is required to seal rigid poly-
propylene vent pipe at the entrance of the chim-
ney or chase to prevent mortar or cement from
contacting the polypropylene vent pipe.
Any termination piping external to the building
must be UV resistant.
Do not apply insulation directly to vent. Maintain
vent manufacturers clearances to combustibles.
Plastic venting systems shall not pass through rat-
ed re separations without approved re stopping
installed in accordance with re stopping manu-
facturers instructions.
Prior to assembly of any joints, ensure joint gasket is
present and properly installed. Contact vent manu-
facturer if gasket is missing or damaged. Verify the in-
tegrity of joints upon completion of the vent system.
WARNING

Table of Contents

Other manuals for IDEAL EXALT COMBI

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the IDEAL EXALT COMBI and is the answer not in the manual?

IDEAL EXALT COMBI Specifications

General IconGeneral
BrandIDEAL
ModelEXALT COMBI
CategoryBoiler
LanguageEnglish

Related product manuals