EasyManua.ls Logo

IDEC HR6S-AF - Signal Interlock Monitoring

IDEC HR6S-AF
93 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Engineering
44
HR9Z-B2192 8/2020
Signal Interlock Monitoring
Overview
Signal interlock is a monitoring function used to detect conditions in which one of the
sensors/devices cannot provide the expected input signal for the device, for example, as a result
of contact welding.
The device expects “simultaneous” deactivation of the two safety-related inputs within the signal
interlock monitoring time of 200 ms.
If the two monitored safety-related inputs are not deactivated within 200 ms, this is a signal
interlock condition and the device triggers a signal interlock alert. The device remains in the defined
safe state, i.e., there is no transition from operating state Run: Outputs Deenergized to operating
state Run: Outputs Energized (T3).
To exit the signal interlock condition, the two affected safety-related inputs must be deactivated for
at least one second. After that, the safety-related inputs can be activated again which activates the
safety-related outputs as well.
Signal interlock is available for certain of the application functions
(see page 58)
the device
provides.
Examples
The following figure illustrates a condition without signal interlock:
Both safety-related inputs are deactivated within the signal interlock monitoring time of 200 ms.
When they are activated again, the safety-related outputs are also activated.
Safety-relaed input S##
Safety-relaed input S##