26: S
CRIPT
26-14 FC6A S
ERIES
MICROS
MART
L
ADDER
P
ROGRAMMING
M
ANUAL
FC9Y-B1726
â– Bit operator
Function
Device, constant, and temporary device are described as , , , ... here.
â– Bit function
â– Word function
Arithmetic operation
Operator Format Description
&
&
Calculates the logical product (AND) of each bit of and .
Data types W (word), I (integer), D (double word), and L (long) can be used. F (float)
cannot be used.
|
|
Calculates the logical sum (OR) of each bit of and .
Data types W (word), I (integer), D (double word), and L (long) can be used. F (float)
cannot be used.
^
^
Calculates the exclusive logical sum (XOR) of each bit of and .
Data types W (word), I (integer), D (double word), and L (long) can be used. F (float)
cannot be used.
~
~
Inverse the logic of each bits of .
For word devices and fixed values, 0 will be 65,535, and 65,535 will be 0.
For bit device, 0 will be 1, and 1 will be 0.
Data types W (word), I (integer), D (double word), and L (long) can be used. F (float)
cannot be used.
<<
<<
Shifts each bit of to the left for bit(s).
Data types W (word), I (integer), D (double word), and L (long) can be used. F (float)
cannot be used.
>>
>>
Shifts each bit of to the right for bit(s).
Data types W (word), I (integer), D (double word), and L (long) can be used. F (float)
cannot be used.
Function Format Description
Bit set
SET( );
Turns bit device to 1.
This is the same result as = 1;.
Bit reset
RST( );
Turns bit device to 0.
This is the same result as = 0;.
Bit reverse
REV( );
Reverses the 1 and 0 of bit device .
This is the same result as = ~ ;.
Function Format Description
Maximum value
MAX( , , )
Maximum value out of , , is returned.
• This can be used for all data types.
• Up to 15 arguments can be defined.
Mininum value
MIN( , , )
Minimum value out of , , is returned.
• This can be used for all data types.
• Up to 15 arguments can be defined.
Exponential
function
EXP( )
Exponential function of is returned.
• This can only be used for data type F (float).
Natural logarithm
(base: e)
LOGE( )
Natural logarithm (base is e) for is returned.
• This can only be used for data type F (float).
• Set a value larger than 0 for argument.
Common logarithm
(Base: 10)
LOG10( )
Common logarithm (base is 10) for is returned.
• This can only be used for data type F (float).
• Set a value larger than 0 for argument.
Exponentiation
POW( , )
to the power is returned.
• This can only be used for data type F (float).

Table of Contents

Other manuals for IDEC MICROSmart FC6A-C24R1CE

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the IDEC MICROSmart FC6A-C24R1CE and is the answer not in the manual?

IDEC MICROSmart FC6A-C24R1CE Specifications

General IconGeneral
BrandIDEC
ModelMICROSmart FC6A-C24R1CE
CategoryComputer Hardware
LanguageEnglish

Related product manuals