EasyManua.ls Logo

IFM AC1402 - Installation; Electrical Connection; Device Supply

IFM AC1402
15 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6
4 Installation
Fix the AS-i Profinet gateway onto a 35 mm DIN rail�
The protection rating of the unit is IP 20, therefore it should be mounted in a
protected location (e�g� control cabinet)�
Ensure a condensation-free environment� Avoid excessive dust, vibration
and shock� The air circulation through the vents must not be impeded�
Avoid installation in direct vicinity of frequency inverters or other interfering
sources�
5 Electrical connection
The device must be connected by a qualified electrician�
Disconnect power before connecting the device�
Observe the national and international regulations for the installation of
electrical equipment�
Connect the device as indicated on the terminals�
Ensure an electrical connection between the AS-i Profinet gateway
(terminal FE) and the ground of the installation�
Only insert or remove the AUX jumper when the device is disconnected�
Otherwise, a device failure may occur
5.1 Device supply
To operate an AS-i system, an AS-i power supply (e�g� AC1236) or the
data decoupling module AC1250 (not supplied) with a DC power supply is
required�
Supply the device with one of the following versions�
5.1.1 Device supply via AUX, AS-i supply via AS-i power supply
Supply the device with a voltage of 24 V DC (18���32 V PELV) (e�g� from the
24 V DN3011 power supply of ifm electronic)� The connection is made to the
terminals X2�
Pull out the AUX jumper
To supply the AS-i lines, connect the terminals X1 to one or two AS-i power
supplies (AC1401: one AS-i master, AC1402: two AS-i masters)�

Other manuals for IFM AC1402

Related product manuals