5 Troubleshooting 
 
 
5
- 33 -
Chapter 5 Troubleshooting
5.1 During Startup
5.1.1 Position Control
During Startup Fault Symptom Cause Conrming Methods
Connect 
control power 
L1C/L2C and 
main power 
L1/L2 and R/S/
T.
The LED display is 
not on or does not 
display "rdy".
1. The control power 
voltage is abnormal.
After disconnecting CN1, CN2, CN3 and CN4, 
the fault persists.
Measure AC voltage between L1C and L2C.
2. The main power 
voltage is abnormal.
For single-phase 220 V model, measure AC 
voltage between L1 and L2. When DC bus 
voltage amplitude (voltage between 
 and 
) 
is lower than 200 V, "nrd" is displayed.
For three-phase 220/380 V model, measure 
AC voltage between R, S and T. When DC bus 
voltage amplitude (voltage between 
 and 
) 
is lower than 460 V, "nrd" is displayed.
3. The program burning 
terminal is shorted.
Check whether the program burning terminal is 
shorted.
4. The servo drive is 
faulty.
-
The operation 
panel displays "Er.
xxx".
Remove the fault.
After the preceding causes are removed, the operation panel should display "rdy".
Set the S-ON 
signal to ON.
The operation 
panel displays "Er.
xxx".
Remove the fault.
Shaft of the servo 
motor is in free 
running status.
1. The S-ON signal is 
invalid.
Set operation panel to servo status display and 
view whether the operation panel displays "rdy" 
rather than "run".
Check whether any parameter in groups H03 
and H17 is set for FunIN1(S-ON). If yes, check 
that the corresponding DI is set to ON. If not, 
allocate the function and set the corresponding 
DI to ON. See group H03 in Chapter 7 for 
details on setting of input terminal parameters.
If a parameter in group H03 has been set for 
FunIN1(S-ON) and corresponding DI is ON, 
but the operation panel still displays "rdy". In 
this case, check whether the DI terminal is 
connected correctly by referring to Chapter 3 in 
the IS650P User Manual.
2. Selection of control 
mode is incorrect.
Check whether H02-00 is set to 1. If it is set to 
2 (torque mode), motor shaft must be in free 
running status because default torque reference 
is 0.
After the preceding causes are removed, the operation panel should display "run".