1 Product Information
- 9 -
1.4 Environment
Environment conditions Indoor, keep away from direct sunlight, no dust, corrosive gas, ammable gas, oil mist, water vapor,
water or salt, for instance.
Altitude Use below 1000 m. The drive power derates 1% at every 100 m altitude increase. The highest
allowed altitude is 3000 m.
Storage Temperature -20°C to +60°C
Operating Temperature -10°C to +50°C. When the temperature is between 40°C to 50°C, the drive output current is derated
1.5% at every 1°C increase. The highest allowed operating temperature is 50°C.
Max. Humidity ≤ 95% RH, no-condensing
Vibration ≤ 5.9 g/s
2
(0.6 g)
Pollution Degree 2
Over-Voltage Category OVC III
Power Supply System
TT/TN
IT (Remove the screws of VDR and EMC lter according to section 2.3.)
Enclosure IP20
1.5 EMC Filter
1.5.1 Internal (Built-in) EMC Filter
Single-phase models with built-in EMC lters as standard, are able to meet the EN61800-3 category C3 emission limits, in order to
comply with the requirements of CE certication by using only the built-in EMC lter in the drive.
1.5.2 External EMC Filter
By using external EMC lters, single-phase model with built-in EMC lters, are able to meet the EN61800-3 C2 emission limits.
Note
Keep the connection cable between the lter and the drive as short as possible (shorter than 30 cm).
Ensure that the EMC lter and the drive are connected to the same grounding surface.
The output ground terminal of the EMC lter should be connected to the input ground terminal of the drive.
The EMC lter must be reliably grounded
.
Failure to comply may result in lter malfunction.
Drive Model
Power Capacity
(kVA)
Input Current
(A)
Single-phase power: 200 V to 240 V, 50/60Hz range: -15% to 10%
MD200S0.4(B)(-NC) 1.7 6.5
MD200S0.75(B)(-NC) 3.0 11.0
MD200S1.5(B)(-NC) 4.8 18.0
MD200S2.2(B)(-NC) 7.1 27.0
Three-phase models with optional external EMC lters are able to meet the EN61800-3 category C3 emission limits, in order to
comply with the requirements of CE certication.
Note
Keep the connection cable between the lter and the drive as short as possible (shorter than 30 cm).
Ensure that the EMC lter and the drive are connected to the same grounding surface.
The output ground terminal of the EMC lter should be connected to the input ground terminal of the drive.
The EMC lter must be reliably grounded
.
Failure to comply may result in lter malfunction.