5 Parameter Table
- 28 -
5 Parameter Table
5.1 Introduction
Groups F and A include standard function parameters. Group U includes the monitoring function parameters and extension card
communication parameters.
5.2 Standard Parameters
Para. No. Para. Name Setting Range Default Comms. Address
Group F0: Standard Parameters
F0-01 Motor 1 control mode
0: Sensorless vector control (SVC)
2: V/F control
2 0xF001/0x0001
F0-02 Command source selection
0: Operating panel
1: Terminal I/O control
2: Serial comms.
0 0xF002/0x0002
F0-03
Main frequency reference setting
channel selection
0: Digital setting (non-retentive at power down)
1: Digital setting (retentive at power down)
2: AI
5: Pulse reference(DI4)
6: Multi-reference
7: Simple PLC
8: PID reference
9: Serial comms.
0 0xF003/0x0003
F0-04
Auxiliary frequency reference
setting channel selection
Same with F0-03 0 0xF004/0x0004
F0-05
Base value of range of auxiliary
frequency reference for main and
auxiliary calculation
0: Relative to maximum frequency
1: Relative to main frequency reference
0 0xF005/0x0005
F0-06
Range of auxiliary frequency
reference for main and auxiliary
calculation
0% to 150% 100% 0xF006/0x0006
F0-07
Final Frequency reference setting
selection
00 to 34 00 0xF007/0x0007
F0-08 Preset frequency 0.00 to maximum frequency (F0-10) 50.00 Hz 0xF008/0x0008
F0-09 Running direction
0: Run in the default direction
1: Run in the direction reverse to the default
direction
0 0xF009/0x0009
F0-10 Max. frequency 50.00 to 500.00 Hz 50.00 Hz 0xF00A/0x000A
F0-11
Setting channel of frequency
upper limit
0: Set by F0-12
1: AI
2: External operating panel
4: Pulse reference (DI4)
5: Communication reference
0 0xF00B/0x000B
F0-12 Frequency reference upper limit F0-14 to F0-10 50.00 Hz 0xF00C/0x000C
F0-14 Frequency reference lower limit 0.00 Hz to frequency upper limit (F0-12) 0.00 Hz 0xF00E/0x000E
F0-15 Carrier frequency 0.8 to 12.0 kHz
Model
dependent
0xF00F/0x000F
F0-16
Carrier frequency adjusted with
temperature
0: Disabled
1: Enabled
1 0xF010/0x0010
F0-17 Acceleration time1
0.00 to 650.00s (F0-19=2)
0.0 to 6500.0s (F0-19=1)
0 to 65000s (F0-19=0)
Model
dependent
0xF011/0x0011