4 Quick Setup
- 27 -
CONTINUE Para. Parameter Name Default Commission
Set V/F parameters. F3-00 V/F curve selection 0
0: Linear V/F
1: Multi-point V/F
F3-01 Torque boost 0.0
0.0 to 30.0 %;
NOTE: If it is 0, automatic torque boost is activated, which is recommended.
F3-02 Frequency limit of torque boost 50.00
0.00 Hz to maximum output frequency
F3-03 Multi-point V/F frequency 1 0.00
0.00 Hz to F3-05
F3-04 Multi-point V/F voltage 1 0.0
0.0 to 100.0 V
F3-05 Multi-point V/F frequency 2 0.00
F3-03 to F3-07, Hz
F3-06 Multi-point V/F voltage 2 0.0
0.0 to 100.0 V
F3-07 Multi-point V/F frequency 3 0.00
F3-05 to rated motor frequency F1-04, Hz
F3-08 Multi-point V/F voltage 3 0.0
0.0 to 100.0 V
Trial RUN Use operating panel, or digital input terminal, or serial communication control, to
start AC drive, check if the running performance satises your application. If yes,
then go forward to the next step, if NO, then go back to check.
Finish