4 Quick Setup
- 27 -
CONTINUE Para. Parameter Name Default Commission
Set V/F parameters. F3-00 V/F curve selection 0
0: Linear V/F
1: Multi-point V/F
F3-01 Torque boost 0.0
0.0 to 30.0 %;
NOTE: If it is 0, automatic torque boost is activated, which is recommended.
F3-02 Frequency limit of torque boost 50.00
0.00 Hz to maximum output frequency
F3-03 Multi-point V/F frequency 1 0.00
0.00 Hz to F3-05
F3-04 Multi-point V/F voltage 1 0.0
0.0 to 100.0 V
F3-05 Multi-point V/F frequency 2 0.00
F3-03 to F3-07, Hz
F3-06 Multi-point V/F voltage 2 0.0
0.0 to 100.0 V
F3-07 Multi-point V/F frequency 3 0.00
F3-05 to rated motor frequency F1-04, Hz
F3-08 Multi-point V/F voltage 3 0.0
0.0 to 100.0 V
Trial RUN Use operating panel, or digital input terminal, or serial communication control, to
start AC drive, check if the running performance satises your application. If yes,
then go forward to the next step, if NO, then go back to check.
Finish