MD280/MD280N User Manual             Parameter Description          
- 147 -
brake time at startup as set, as shown in Fig.6-12.   
DC brake current at startup: The DC brake quantity added shall be set 
according to the percentage setting of the rated current of the inverter. The 
higher the brake current is, more powerful the brake effect is.   
DC brake time at startup: It refers to the continuous DC brake time. If it is 
set to 0, the inverter will be started directly without undergoing DC brake.   
Output Frequency Hz
Output Voltage ˄V˅
Effective Value 
DC Brake Quantity at Startup 
Running Command 
DC Brake Current at Startup 
Time 
Time 
Output Frequency Hz
Output Voltage ˄V˅
Effective Value 
DC Brake Quantity at Startup 
Running Command 
DC Brake Current at Startup 
Time 
Time 
 
Fig6-13 Schematic Diagram for Brake Current at Startup 
 
Speed-up/speed-down 
mode 
Factory 
default 
value 
0 
0 Straight 
speed-up/speed-down 
1 S curve 
speed-up/speed-down 
mode A 
F4-07 
Setup range 
2 S curve 
speed-up/speed-down 
mode B 
It is used to select the frequency change mode during the inverter start and 
stop process. 
MD280 series inverter provides two types of speed-up/speed-down times, 
0: Straight speed-up/speed-down 
The output frequency increases or decreases along the straight line. It can 
select speed-up/speed-down time via the multifunctional digital input 
terminals 
 