MD280/MD280N User Manual                              Fault Diagnosis and Countermeasures             
- 213 -
8.2 Common Fault and Resolution 
During the inverter using process, the following faults may occur. Please 
conduct simple fault analysis by referring to the methods below:   
No.
Fault 
Phenomenon 
Possible Cause  Solution 
1 
No display or 
error codes 
occur upon 
power-on 
1ǃ The inverter has abnormal 
input power supply.   
2 ǃ 8-core and 16-core bus 
connecting with the drive board 
and control panel is in poor 
contact.  
3 ǃ The internal parts of the 
inverter are damaged. 
a) Check  the 
input power supply.   
b) Plug/unplug 
the 8-core and 
16-core buses once 
again.  
c) Consult the 
manufacturer. 
2 
 “ERR23” 
alarm is 
displayed 
upon 
power-on 
1. The motor or the 
output line is short 
circuited to the 
earth.  
2ǃThe inverter is damaged. 
1ǃMeasure the insulation 
of the motor and output 
line with 
magneto-ohmmeter.  
2 ǃ Consult the 
manufacturer. 
3 
The inverter 
displays 
normally upon 
power-on, but 
“HC” is 
displayed 
upon running 
and stops 
immediately. 
The fan is either damaged or 
blocked. 
Replace the fan 
4 
ERR14 
(module 
overheating) 
fault is 
frequently 
 
1ǃ  The carrier frequency 
is set too high.   
2ǃ  The fan is damaged or 
the air duct is blocked.   
1 ǃ Reduce the carrier 
frequency. 
2ǃReplace the fan and 
clear the air duct.   
3 ǃ Consult the 
 