meter to control the insulation of the circuit.    It is not necessary to conduct 
the high voltage test (which has been completed upon delivery).   
2.7.3 Replacement of Vulnerable Parts for Inverter 
The vulnerable parts of the inverter include cooling fan and filter electrolytic 
capacitor, whose life depends on the operating environment and 
maintenance status. Common service life: 
 
Part name  Life time 
Fan  2 to 3 years 
Electrolytic 
capacitor
 
4 to 5 years 
The user can determine the term for replacement according to the running 
time.  
1˅ Cooling fan 
Possible causes for damage: bearing wearing and blade aging.   
Criteria: Whether there is crack on the blade and whether there is abnormal 
vibration noise upon startup.   
2˅  Possible causes for damage of filter electrolytic capacitor: Poor 
input source quality, high ambient temperature, frequent load jumping 
and burning electrolyte.   
Criteria: Whether there is liquid leakage, whether the safe valve has 
projected, measure the static capacitance, and measure the insulating 
resistance.  
2.7.4 Storage of Inverter 
Attention shall be paid to the following points for the temporary and 
long-term storage of the inverter:   
1) Place the inverter back into the packing box following the original 
package  
2) Long-term storage will degrade the electrolytic capacitor. The product 
shall be powered up once every 2 years, and the power-up time shall be no 
less than 5 hours. The input voltage shall be increased slowly to the rated 
value with the regulator.   
2.8 Instructions on Warranty of Inverter 
Free warranty only applies to the inverter itself.   
 