MD280/MD280N User Manual Parameter Description
- 177 -
0 Power fault without memory
Setup range
1 Power fault memory
PLC power fault memory: The PLC running phase before power fault is
memorized. If it runs upon power on, it will run from the memorizing phase.
Running time unit
Factory default
value
0
0 s (second)
F8-11
Setup
range
1 h (hour)
It is used to set the time unit of running at each phase and can select such
time units as second and hour.
Caution: Stop without memory
Running time of zero
segment of PLC
Factory default
value
0.0s(h)
F8-12
Setup range 0.0s(h) to 6553.5s(h)
Speed-up/speed-down
time selection of zero
segment of PLC
Factory default
value
0
0 Speed-up/speed-down 1
F8-13
Setup range
1 Speed-up/speed-down 2
Running time of the
first segment of PLC
Factory default
value
0.0s(h)
F8-14
Setup range 0.0s(h) to 6553.5s(h)
Speed-up/speed-down
time selection of the first
segment of PLC
Factory default
value
0
0 Speed-up/speed-down 1
F8-15
Setup range
1 Speed-up/speed-down 2
Running time of the
second segment of
PLC
Factory default
value
0.0s(h)
F8-16
Setup range 0.0s(h) to 6553.5s(h)
Speed-up/speed-down
time selection of the
second segment of
PLC
Factory default
value
0
0 Speed-up/speed-down 1
F8-17
Setup range
1 Speed-up/speed-down 2