MD280/MD280N User Manual Parameter Description
- 187 -
F
B
-
2
7
Outpu
t
termi
nal
statu
s
upon
fault
This value
is a
decimal
number. It
displays
the status
of all the
digital
output
terminals
of the last
fault in the
following
sequence
:
BIT7
BI
T
6
BIT
5
BIT
4
BIT
3
BIT
2
BI
T1
BIT0
reserved Re
ser
ve
d
reser
ved
reser
ved
D
O
3
D
O
2
D
O
1
REA
LY
It is displayed in decimal numbers corresponding to the
status of each digit. When the output terminal is ON, the
corresponding value is 1. When the output terminal is
OFF, the value is 0.
Under-voltage point selection
Factory
default
value
100.0%
FB-28
Setup
range
60.0% to 140.0%
Three phase: 100.0% corresponding bus
voltage 350.0V
Two phase: 100.0% corresponding bus
voltage 200.0V
The function is used in the applications where the under-voltage point is
required to be changed.
If it is the three-phase inverter, 100.0% corresponding 350.0V, it indicates
that enter the under-voltage status when the bus voltage is below 350.0V.
efesotomasyon.com