Digital output terminal control: ˄Write-only˅
Command word addr.
Command function
6000H
BIT0˖ Output control
BIT1˖ DO2 output control
BIT2˖ RELAY1 output control
BIT3˖ Reserved
BIT4˖ DO3 output control
Analog output AO1 control: (Write-only)
Command word addr. Command function
7000H
07ffff refers to 0ˁ100ˁ
Pluse output control: (write-only)
Address of locking
password command
Contents of locking password command
A000H
07fff refers to 0ˁ100ˁ
Inverter fault description:
Inverter fault address Inverter fault information
8000H
0000˖ No fault
0001˖ Reserved
0002˖ Speed-up over current
0003˖ Speed-down over current
0004˖ Contant over current
0005˖ Speed-up over voltage
0006˖ Speed-down over voltage
0007˖ Contant speed over voltage
0008˖ Buffer resistance overload
0009˖ Under-voltage fault
000A˖ Inverter overload
000B˖ Motor overload
000C˖ Input phase fault
000D˖ Output phase faulure
000E˖ Module overheating
000F˖ External fault
0010˖ Communication fault
0011˖ Contactor fault
0012˖ Current detection fault
0013˖ Motor tuning fault
0014˖ Reserved
0015˖ EEPROM read and write fault
efesotomasyon.com