55
Deceleration overvoltage
Whether the input voltage is too high
Whether there is external force
drivi ng the motor during the operation
Whether the acceleration time is too short
Whether the braking resistor is installed
Seek for technical support from
the manufacturer or supplier
Adjust the voltage to normal
Remove the external force
or install braking resistor
Increase the acceleration time
Install the braking resistor
Deceleration overvoltage
Whether the input voltage is too high
Whether there is external force
drivi ng the motor during the operation
Whether the acceleration time is too short
Whether the braking resistor is installed
Seek for technical support from
the manufacturer or supplier
Adjust the voltage to normal
Remove the external force
or install braking resistor
Increase the acceleration time
Install the braking resistor
Figure 7-6 Deceleration overvoltage (ERROR06)