MD380 User Manual Function Code Table
- 99 -
Function
Code
Parameter Name
Setting Range
Default Property
F8-05 Acceleration time 3
0.0–6500.0s
Model
dependent
☆
F8-06 Deceleration time 3
0.0–6500.0s
Model
dependent
☆
F8-07 Acceleration time 4
0.0–500.0s
Model
dependent
☆
F8-08 Deceleration time 4
0.0–6500.0s
Model
dependent
☆
F8-09 Jump frequency 1
0.00 Hz to maximum frequency
0.00 Hz ☆
F8-10 Jump frequency 2
0.00 Hz to maximum frequency
0.00 Hz ☆
F8-11 Frequency jump amplitude
0.00 Hz to maximum frequency
0.00 Hz ☆
F8-12
Forward/Reverse rotation
dead-zone time
0.0–3000.0s
0.0s ☆
F8-13 Reverse control
0: Enabled
1: Disabled
0 ☆
F8-14
Running mode when set
frequency lower than
frequency lower limit
0: Run at frequency lower limit
1: Stop
2: Run at zero speed
0 ☆
F8-15 Droop control
0.00–10.00 Hz
0.00 Hz ☆
F8-16
Accumulative power-on time
threshold
0–65000 h
0 h ☆
F8-17
Accumulative running time
threshold
0–65000 h
0 h ☆
F8-18 Startup protection
0: No
1: Yes
0 ☆
F8-19
Frequency detection value
(FDT1)
0.00 Hz to maximum frequency
50.00 Hz ☆
F8-20
Frequency detection
hysteresis (FDT hysteresis 1)
0.0%–100.0% (FDT1 level)
5.0% ☆
F8-21
Detection range of frequency
reached
0.00–100% (maximum frequency)
0.0% ☆
F8-22
Jump frequency during
acceleration/deceleration
0: Disabled1: Enabled
0 ☆
F8-25
Frequency switchover point
between acceleration time 1
and acceleration time 2
0.00 Hz to maximum frequency
0.00 Hz ☆
F8-26
Frequency switchover point
between deceleration time 1
and deceleration time 2
0.00 to maximum frequency
0.00 Hz ☆
F8-27 Terminal JOG preferred
0: Disabled1: Enabled
0 ☆