MD380 User Manual Function Code Table
- 89 -
Function
Code
Parameter Name
Setting Range
Default Property
F4-05 DI6 function selection
30: Pulse input (enabled only for
DI5)
31:Reserved
32: Immediate DC braking
33: Normally closed (NC) input of
external fault
34: Frequency modication
forbidden
35: Reverse PID action direction
0 ★
F4-06 DI7 function selection
36: External STOP terminal 1
37: Command source switchover
terminal 2
38: PID integral pause
39: Switchover between main
frequency source X and preset
frequency
0 ★
F4-07 DI8 function selection
40: Switchover between auxiliary
frequency source Y and preset
frequency
41: Motor selection terminal 1
42: Motor selection terminal 2
43: PID parameter switchover
0 ★
F4-08 DI9 function selection
44: User-dened fault 1
45: User-dened fault 2
46: Speed control/Torque control
switchover
47: Emergency stop
0 ★
F4-09 DI10 function selection
48: External STOP terminal 2
49: Deceleration DC braking
50: Clear the current running time
51: Switchover between two-line
mode and three-line mode
52–59: Reserved
0 ★
F4-10 DI lter time
0.000–1.000s
0.010s ☆
F4-11 Terminal command mode
0: Two-line mode 1
1: Two-line mode 2
2: Three-line mode 1
3: Three-line mode 2
0 ★
F4-12 Terminal UP/DOWN rate
0.01–65.535 Hz/s
1.00 Hz/s ☆
F4-13 AI curve 1 minimum input
0.00 V to F4-15
0.00 V ☆