6. Description of Parameters                                                                                                                   
- 144 -
Function Code Parameter Name Setting Range Default
F9-59
Power dip ride-through 
function selection
0: Disabled
1: Bus voltage constant control
2: Decelerate to stop
0
F9-60
Threshold of power dip ride-
through function disabled
85% to 120% 85%
F9-61
Judging time of bus voltage 
recovering from power dip
0.1s to 10.0s 0.5s
F9-62
Threshold of power dip ride-
through function enabled
60% to 85% (standard bus voltage) 80.0%
F9-71
Power dip ride-through gain 
Kp
0 to 100 40
F9-72
Power dip ride-through 
integral coefcient
0 to 100 30
F9-73
Deceleration time of power 
dip ride-through
0.0s to 300.0s 20.0s
 ● In bus voltage constant control, when line voltage recovers, the AC drive 
accelerates to target frequency. 
 ● In deceleration to stop mode, when line voltage recovers, the AC drive continues 
to decelerate to 0 Hz and stops. The AC drive will not be started until it receives 
RUN command again.
6.6.7  Load Lost Protection
Function Code Parameter Name Setting Range Default
F9-63
Load lost protection 0: Disabled
1: Enabled
0
F9-64
Load lost detection level 0.0% to 100.0% (rated motor current) 10.0%
F9-65
Load lost detection time 0.0s to 60.0s 1.0s
These function parameters dene the load lost protection function. 
When output current of the AC drive falls below detection level (F9-64) for longer than time set in 
F9-65, the AC drive automatically reduces output frequency to 7% of rated frequency. Once load 
recovers during protection, the AC drive accelerates to frequency reference.