6 Parameter Description
-
193
-
Function
Code
Name Setting Range Default Unit Property
F3-09 Pre-deceleration distance 0 to 90.0 0.0 mm
F3-09 is used to set the pre-deceleration distance of the elevator in distance control,
󶍽
leveling signal delay.
Function
Code
Name Setting Range Default Unit Property
F3-10 Re-leveling speed 0.020 to 0.080 0.040 m/s
F3-10 is used to set the elevator speed during re-leveling.
This parameter is valid only when the pre-open module (MCTC-SCB-A) is added to
implement the re-leveling function (set in FE-32).
Function
Code
Name Setting Range Default Unit Property
F3-11 Inspection speed 0.100 to 0.630 0.250 m/s
F3-11 is used to set the elevator speed during inspection.
Function
Code
Name Setting Range Default Unit Property
F3-12 Position of up slow-down 1 0.00 to 300.00 0.00 m
F3-13 Position of down slow-down 1 0.00 to 300.00 0.00 m
F3-14 Position of up slow-down 2 0.00 to 300.00 0.00 m
F3-15 Position of down slow-down 2 0.00 to 300.00 0.00 m
F3-16 Position of up slow-down 3 0.00 to 300.00 0.00 m
F3-17 Position of down slow-down 3 0.00 to 300.00 0.00 m
F3-12 to F3-17 specify the positions of all slow-down switches relative to the bottom
leveling position, and the positions are automatically recorded during shaft auto-
tuning. For the installation positions of the slowdown switches, see 2.4.2 Slow-Down
Switches.
The NICE3000
new
supports a maximum of three pairs of slow-down switches. From
two sides of the shaft to the middle, slow-down 1, slow-down 2, and slow-down 3 are
󶍿
be only one pair of slow-sown switches for the low-speed elevator, and two or three
pairs of slow-down switches for the high-speed elevator.
The system automatically detects the speed when the elevator reaches a slow-down
switch. If the detected speed or position is abnormal, the system enables the elevator
to slow down at the special deceleration rate set in F3-08, preventing over travel top
terminal or over travel bottom terminal.