4 Parameter Description
4
Parameter
No.
Parameter Name Setting Range Default Unit
Property
F6-44 is used to select the re emergency-related functions. Each bit of the parameter denes a function, as
described in the following table.
If a bit is set to 1, the function indicated by this bit is enabled; if this bit is set to 0, the function is disabled. For
details on how to view and set this parameter, see the descriptions in section 8.21.1.
The functions dened by the binary bits of F6-44 are described in the following table.
Bit Function Description Default
Bit0
to
Bit2
Reserved - 0
Bit3
Arrival gong output
in inspection or re
emergency state
The arrival gong is output in the inspection or re emergency
state.
0
Bit4
Multiple car calls
registered in re
emergency state
Multiple car calls can be registered in the re emergency state. If
this function is disabled, only one car call can be registered.
0
Bit5
Retentive at power failure
in re emergency state
In the re emergency state, the current system and car state will
be memorized at power failure and be resumed after the system is
powered on again.
0
Bit6
Closing door by holding
down the door close
button
In the re emergency state, the door close process can be
completed only by holding down the door close button until the
door close limit is reached. Otherwise, it will be switched over to
door open automatically.
0
Bit7 Reserved - 0
Bit8
Door close at car call
registering
The elevator enters the door close process automatically if a car
call is registered.
0
Bit9
Displaying hall calls in re
emergency state
Hall calls are displayed in the re emergency state. 0
Bit10 Fireghter forced running
JP22 is used for reghter forced running input.
In the reghter running state, when the JP22 input switch and the
door close button are enabled simultaneously, the buzzer tweets
and the system outputs the door close signal. If the door lock
is not enabled within 10s, the system outputs the shorting door
lock circuit contactor signal, and the elevator starts running (used
together with SCB-A).
0
Bit11
Exiting reghter state
upon arrival at re
emergency oor
The system can exit the reghter state only after the elevator
arrives at the re emergency oor.
0
Bit12
Not clearing car calls
at reverse door open in
reghter running state
In the reghter running state, the car calls that have been
registered are not cleared at reverse door open.
0
Bit13 Reserved - 0
Bit14
Opening door by holding
down the door open
button
In the re emergency state, the door open process can be
completed only by holding down the door open button until the
door open limit is reached. Otherwise, it will be switched over to
door close automatically.
0
Bit15
Automatic door open at
re emergency oor
The door opens automatically after the elevator arrives at the re
emergency oor.
0