4 Parameter Description
4
Parameter
No.
Parameter Name Setting Range Default Unit
Property
FE-52 to FE-56 are used to set special īoor display.
When the 2-digit display cannot meet the requirement, you can add the third-digit display by setting these
parameters as follows:
1. Set the two high digits for indicating the īoor address that requires special display, and set the two low digits
for indicating the display content.
For example, if īoor 18 needs to be displayed as ā17Aā, set FE-18 to 0710 (displaying ā7Aā) and then set the
FE-52 to 1801 (displaying ā1ā).
Figure 4-9 Setting īoor 18 display to ā17Aā
FE-52 = 1801
FE-18 (Floor 18 display)
= 0710
01
Floor address for
special display ("18")
Special display
content ("1")
18 10
Display "7" Display "A"
07
1
7A
Floor 18 display
2. Set F8-14 Bit0 to 1.
3. Power off the system and power it on again.
FE-32
Elevator function
selection 1
Bit2: Re-leveling function
Bit3: Door pre-open function
Bit4: Stuck hall call cancellation
Bit5: Night security īoor function
Bit6: Down collective selective
peak service
Bit7: Parallel/Group control peak
service
Bit8: Time-based service īoor
function
Bit9: VIP function
Bit11: Car call deletion
Bit12: Hall call deletion
34816 -