- 123 -
4 Parameter Description
4
Parameter
No.
Parameter Name Setting Range Default Unit
Property
Fr-20
Leveling adjustment
record 20
0 to 60060 30030 mm
ā˜…
Fr-01 to Fr-20 record the leveling adjustment values. Each parameter records the adjustment information of two
oors, and therefore, the adjustment information of 40 oors can be recorded totally.
The method of viewing the record is shown in the following gure.
Figure 4-10 Viewing the leveling adjustment record
Second floor leveling First floor leveling
...
...
> 30: upward leveling adjustment
= 30: no leveling adjustment
< 30: downward leveling adjustment
Maximum
adjustment
range: ±30mm
As shown in the preceding gure, the left two LEDs and the right two LEDs respectively show the adjustment
bases of the rst oor and second oor. If the value is larger than 30, it is upward leveling adjustment; if the value
is smaller than 30, it is downward leveling adjustment. The default value ā€œ30ā€ indicates that there is no leveling
adjustment. The maximum adjustment range is ±30 mm.
The leveling adjustment method is as follows:
Ensure that shaft auto-tuning is completed successfully, and the elevator runs properly at normal speed.
Set Fr-00 to 1 to enable the car leveling adjustment function. Then, the elevator shields hall calls, automatically
runs to the top oor, and keeps the door open after arrival. If the elevator is at the top oor, it directly keeps the
door open.
Go into the car, press the top oor button on the CCB once, and the leveling position is changed 1 mm upward;
press the bottom oor button on the CCB once, and the leveling position is changed 1 mm downward. The value
is displayed on the car display board.
Positive value: up arrow + value, negative value: down arrow + value, adjustment range: ±30 mm
After completing adjustment for the present oor, press the top oor button and bottom oor button at the same
time to save the adjustment result. The car display restores to the normal state. If the leveling position of the
present oor need not be adjusted, press the top oor button and bottom oor button at the same time to exit the
leveling adjustment state. Then, car calls can be registered.
Press the door close button, and press the button for the next oor. The elevator runs to the next oor and keeps
the door open after arrival. Then, you can perform leveling adjustment.
After completing adjustment for all oors, set Fr-00 to 0 to disable the leveling adjustment function. Otherwise, the
elevator cannot be used.
Group E0: 1st fault details
The system prompts and records faults. The keypad displays the fault code and subcode in scrolling mode, for
example, ā€œ E22-101
E0-00 1st fault code 0 to 9999 0