EasyManua.ls Logo

Inovance Monarch NICE-L-C-2003 - Page 88

Inovance Monarch NICE-L-C-2003
152 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
- 87 -
4 Parameter Description
4
Parameter
No.
Parameter Name Setting Range Default Unit
Property
F5-24 X24 function selection
... (Continued)
80/112: Terminal oor verication
signal NO/NC
81/113: Door lock 1 shorting NO/
NC
(End)
00 -
ā˜…
F5-25 CTB input type 0 to 511 320 -
ā˜…
Bit of F5-25 CTB Input Signal
Bit0 Used to set NO/NC feature of door 1 light curtain signal
Bit2 Used to set NO/NC feature of door 1 open limit signal
Bit4 Used to set NO/NC feature of door 1 close limit signal
F5-26 Y1 function selection
00: No function
01: RUN contactor control
02: Brake contactor control
03: Shorting door lock circuit relay
output
04: Fire emergency oor arrival
feedback
Others:
00: Invalid
05: Door machine 1 open
06: Door 1 close
07: Door 2 open
08: Door 2 close
09: Brake and RUN contactors
healthy
10: Fault state
11: Running monitor
12: Shorting PMSM stator
contactor
13: Emergency evacuation
automatic switchover
14: System healthy
15: Emergency buzzer control
16: Higher-voltage startup of brake
17: Elevator running in up direction
18: Lamp/Fan running
19: Medical sterilization
20: Non-door zone stop
21: Electric lock
22: Non-service state
23: Emergency evacuation
completed
1 -
ā˜…
F5-27 Y2 function selection 2 -
ā˜…
F5-28 Y3 function selection 3 -
ā˜…
F5-29 Y4 function selection 4 -
ā˜…
F5-30 Y5 function selection 0 -
ā˜…
F5-31 Y6 function selection 0 -
ā˜…
F5-32
Communication state
display
- - -
ā—

Other manuals for Inovance Monarch NICE-L-C-2003

Related product manuals