- 143 -
5 Troubleshooting
5
Fault Code Name Possible Causes Solution Level
Err46
Re-leveling
abnormal
Subcode 101: The
leveling signal is
inactive during re-
leveling.
Check whether the leveling signal is normal.
2B
Subcode 102: The
re-leveling running
speed exceeds 0.1 m/
s.
Check whether the encoder is used properly.
Err47
Shorting door
lock circuit relay
abnormal
Subcode 101: During
re-leveling or pre-
open running, the
shorting door lock
circuit contactor
outputs for continuous
2s, but the feedback
is invalid and the door
lock is disconnected.
Check the signal feature (NO, NC) of the
feedback contact on the shorting door lock
circuit contactor.
Check whether the shorting door lock circuit
contactor acts properly.
2B
Subcode 102: During
re-leveling or pre-
open running, the
shorting door lock
circuit contactor has
no output, but the
feedback is valid for
continuous 2s.
Subcode 106: The
feedback from the
shorting door circuit
relay is valid before
re-leveling.
Subcode 103: During
re-leveling or pre-
open running, the
output time of the
shorting door lock
circuit contactor is
larger than 15s.
Check whether the leveling and re-leveling
signals are normal.
Check whether the re-leveling speed is set
too small.
Err48
Door open fault
Subcode 101: The
consecutive times
that the door does
not open to the limit
reaches the setting in
Fb-09.
Check whether the door machine system
works properly.
Check whether the CTB output is normal.
Check whether the door open limit signal and
door lock signal are normal.
5A
Err49
Door close fault
Subcode 101: The
consecutive times
that the door does
not open to the limit
reaches the setting in
Fb-09.
Check whether the door machine system
works properly.
Check whether the CTB output is normal.
Check whether the door close limit signal
and door lock signal are normal.
5A
Err50
Consecutive loss
of leveling signal
Subcode 101:
Leveling signal stuck
is detected for three
consecutive times.
Check whether the leveling and door zone
sensors work properly.
Check the installation verticality and depth of
the leveling plates.
Check the leveling signal input points of the
MCB.
Check whether the steel rope slips.
5A
Subcode 102:
Leveling signal loss
is detected for three
consecutive times.