11.2.8 Hot water does not reach temperature
Possible causes: Solution:
DHW flow to high. Adjust the inlet assembly.
No
Temperature setting for water circuit too low. Set the hot water circuit, depending on the desired temperature.
No
No heat transfer as a result of lime scale or
fouling in the heat exchanger DHW side.
Descale or flush the exchanger DHW side.
No
Cold water temperature <10°C.
11.2.9 LED on CH pump is flashing alternately red and green.
Possible causes: Solution:
Mains voltage to high or to low. Check the mains.
No
Temperature of the pump is to high
Check the water and environment temperature.
11.2.10 LED on CH pump is flashing red.
Possible causes: Solution:
Pump is not running
Reset the pump by shutting of the boiler (stand-by or powerless) for at least 20
seconds.
Note: If the pump is set on “continuously active” (parameter 2 = 1) the boiler must
be made powerless for at least 20 seconds.