166  Advisor Advanced ATSx000A(-IP) Installation and Programming Manual 
9.1.n.8.1.1 Area modifier 
 
If the Area modifier option is set to Yes, the area modifier is added to the SIA and 
XSIA reports. This allows you to send event from multiple areas using the same 
account code. See also “9.1.n.5 Accounts” on page 164. 
9.1.n.8.1.2 Name chars 
 
The Name chars value defines the length of the name strings used in the XSIA 
reporting. 
The allowed values are 16 and 30. 
9.1.n.8.1.3 Event number 
 
3 Event number 
      >3 digits< 
The Event number value defines the length of the subevent field (user or point). 
The allowed values are 2, 3, and 4 digits. 
9.1.n.8.1.4 Subev coding 
 
The Subev coding value defines whether the subevent number is reported to the 
CS in hexadecimal (hex) or decimal format. 
9.1.n.8.1.5 SIA frequency 
 
The SIA frequency menu allows you to select one of two standards for modem 
communication regarding transmitted/received frequencies used by 
transmitter/receiver.  
This option allows you to select between CCITT and BELL. 
9.1.n.8.2 VOICE 
 
The VOICE menu allows you to configure voice reporting options listed below.