Goodrive10 Series Mini VFD    Fault tracking 
-79- 
Check  whether  there  are  foreign 
matters blocking or attached to the 
cooling  fan,  air  inlets,  or  air 
outlets. 
6.1.2 Cooling fan 
The service life of the cooling fan of the VFD is more than 25,000 hours. The actual service 
life of the cooling fan is related to the use of the VFD and the temperature in the ambient 
environment. You can view the running duration of the VFD through P07.14 (Accumulated 
running time). 
The increase of the bearing noise indicates a fan fault. If the VFD is applied in a key position, 
replace the fan once the fan starts to generate unusual noise. You can purchase spare parts 
of fans from INVT. 
  Read  and  follow  the  instructions  in  chapter  1  "Safety  precautions". 
Ignoring  the  instructions  would  cause  physical  injury  or  death,  or 
damage to the equipment.   
1.  Stop the VFD and disconnect it from the AC power source and wait for at least the time 
designated on the VFD. 
2.  Lever  the  fan  mounting  plate  from  the  cabinet  with  a  screwdriver,  and  lift  the  fan 
mounting plate slightly upward. 
3.  Disconnect the fan cable. 
4.  Remove the fan cable, and remove the fan mounting plate. 
5.  Install the new fan mounting plate including the fan back to the VFD in reverse order. 
6.  Power on the VFD. 
6.1.3 Capacitors 
Capacitor reforming 
If the VFD has been left unused for a long time, you need to follow the instructions to reform 
the DC bus capacitor before using it. The storage time is calculated from the date the VFD is 
delivered. 
No charging operation is required. 
The VFD needs to be powered on for 1 hour before the first 
running command.