includes:  start,  stop,  forward/reverse 
rotating, jogging and fault reset. 
0:  Keypad  running  command  channel 
(“LOCAL/REMOT” light off) 
Carry out  the command control by  RUN, 
STOP/RST  on  the  keypad.  Set  the 
multi-function  key  QUICK/JOG  to 
FWD/REV shifting function (P07.02=3) to 
change the running direction; press  RUN 
and STOP/RST simultaneously in running 
state to make the VFD coast to stop. 
1:  Terminal  running  command  channel 
(“LOCAL/REMOT” flickering) 
Carry out the running command control by 
the forward rotation, reverse  rotation and 
forward jogging and reverse jogging of the 
multi-function terminals. 
2:  Communication  running  command 
channel (“LOCAL/REMOT” on); 
The running command is controlled by the 
upper monitor via communication. 
This  parameter  is  used  to  set  the 
maximum  output  frequency  of  the  VFD. 
Users  need  to  pay  attention  to  this 
parameter because it is the foundation of 
the  frequency  setting  and  the  speed  of 
acceleration and deceleration.   
Setting range: P00.04–400.00Hz