Goodrive100-PV Series Solar Pumping VFD   Function parameters 
58 
Detailed illustration of parameters 
voltage  loop  uses  this  group  PI 
parameter. Otherwise, the boost voltage 
loop uses the first group PI parameter. 
Setting range: 0.000–65.535 
If  the  difference  between  the  bus 
reference  voltage  and  actual  bus 
voltage  is  greater  than  20V,  the  boost 
voltage loop  uses the PI parameters  of 
this group. Otherwise, the boost voltage 
loop uses the PI parameters of the first 
group. 
Setting range: 0.000–65.535 
Once being powered, the boost module 
sends  its  version  information  to  the 
inverter side. 
Note: 
  The time when the pump VFD operated to the lower limit of PI output frequency after VFD 
start-up is determined by the ACC time. 
  Delay time counting follows the rules if multiple fault conditions are met simultaneously: For 
example, if all fault conditions of weak light, full water, and underload are met at the same 
time, the VFD will count the delay time for each fault independently. If the delay time of a 
fault is reached, the fault is reported. The delay time counting of the other two faults keeps. 
If the reported fault is resolved but the conditions of the other two faults persist, the delay 
time counting of the other two faults continues. If a fault condition is not met during counting, 
the delay time of this fault is cleared.