Goodrive100-PV Series Solar Pumping VFD  Fault diagnosis and solution 
60 
2.  The  voltage  of  the  grid  is 
too low. 
3.  The  power  of  the  VFD  is 
too low.   
4.  The  load  transients  or  is 
abnormal. 
5.  The  grounding  is  short 
circuited  or  the  output  is 
phase loss.   
6.  There  is  strong  external 
interference.   
7.  The  overvoltage  stall 
protection is not open. 
3.  Select  the  VFD  with  a  larger 
power. 
4.  Check  if  the  load  is  short 
circuited  (the  grounding  short 
circuited  or  the  wire  short 
circuited)  or  the  rotation  is  not 
smooth.   
5.  Check  the  output 
configuration.   
6.  Check  if  there  is  strong 
interference.   
7.  Check  the  setting  of  relative 
function codes. 
Constant-speed 
overcurrent 
1.  The  voltage  of  the  power 
supply is too low. 
2.  The  overvoltage  stall 
protection is not open. 
1. Check the input  power of  the 
supply line. 
2.  Check  the  setting  of  relative 
function codes. 
1.  The  voltage  of  the  power 
supply is too low. 
2.  The  motor  setting  rated 
current is incorrect.   
3.  The  motor  stall  or  load 
transients is too strong. 
1. Check the power of the supply 
line.   
2. Reset the rated current of the 
motor. 
3. Check the load and adjust the 
torque lift. 
1. The acceleration is too fast. 
2. The rotating motor is reset.   
3.  The  voltage  of  the  power 
supply is too low.   
4. The load is too heavy.   
5.  The  motor  power  is  too 
small. 
1. Increase the ACC time. 
2.  Avoid  the  restarting  after 
stopping.   
3. Check the power of the supply 
line. 
4.  Select  a  VFD  with  bigger 
power. 
5. Select a proper motor. 
Phase  loss  or  fluctuation  of 
input R,S,T 
1. Check input power.   
2. Check installation distribution. 
U,V,W  phase  loss  output  (or 
serious  asymmetrical  three 
1. Check the output distribution.   
2. Check the motor and cable.