7.4.4 Fault message response   
There may be fault in the communication control. For example, some parameter can only be read. If a writing 
message is sent, the inverter will return a fault response message.   
The fault message is from the inverter to the master, its code and meaning is as below:   
Code  Name  Meaning 
01H  Illegal command 
The command from master can not be executed. The reason maybe: 
1. This command is only for new version and this version can not realize.
2. Slave is in fault state and can not execute it. 
02H 
Illegal data 
address. 
Some of the operation addresses are invalid or  not allowed  to access. 
Especially the combination of the register and the transmitting bytes are 
invalid.   
03H  Illegal value 
When there are invalid data in the message framed received by slave. 
Note: This error code does not indicate the  data value to  write exceed 
the range, but indicate the message frame is an illegal frame. 
04H  Operation failed 
The parameter setting in parameter  writing is invalid. For example, the 
function input terminal can not be set repeatedly.   
05H  Password error 
The password written to the password check address is not same as the 
password set by P7.00. 
06H  Data frame error 
In the frame message sent by the upper monitor, the length of the digital 
frame is incorrect or the counting of CRC check bit in RTU is different 
from the lower monitor.   
07H 
Written not 
allowed. 
It only happen in write command, the reason maybe: 
1. The written data exceeds the parameter range. 
2. The parameter should not be modified now. 
3. The terminal has already been used. 
08H 
The parameter 
can not be 
modified during 
running 
The  modified parameter  in the writing of the upper monitor can  not  be 
modified during running.   
09H 
Password 
protection 
When the  upper monitor is writing or reading and the user password is 
set without password unlocking, it will report that the system is locked.   
The slave uses functional code fields and fault addresses to indicate it is a normal response or some error 
occurs  (named  as  objection  response).  For  normal  responses,  the  slave  shows  corresponding  function 
codes, digital address or sub-function codes as the response. For objection responses, the slave returns a 
code which equals the normal code, but the first byte is logic 1. 
For example: when the master sends a message to the slave, requiring it to read a group of address data of 
the inverter function codes, there will be following function codes:   
          0 0 0 0 0 0 1 1 (Hex 03H)   
For normal responses, the slave responds the same codes, while for objection responses, it will return: 
1 0 0 0 0 0 1 1 (Hex 83H)   
Besides  the function  codes  modification  for the objection  fault,  the  slave  will  respond  a  byte of  abnormal 
code which defines the error reason.