Times of motor overload M = Iout/(In×K)   
In  is  the  rated  current  of  the  motor,  Iout  is  the 
output  current  of  the  VFD  and  K  is  the  motor 
protection coefficient.   
The smaller K is, the greater M is, and the more 
likely protection is implemented. 
When  M=116%,  protection  is  performed  after 
motor overload lasts for 1 hour;  when M=150%, 
protection is performed after motor overload lasts 
for  12  minutes;  when  M=180%,  protection  is 
performed  after  motor  overload  lasts  for  5 
minutes; when M=200%, protection is performed 
after  motor  overload  lasts  for  60  seconds;  and 
when  M ≥   400%,  protection  is  performed 
immediately. 
Correct the power displaying of motor 2.   
Only  impact  the  displaying value  other  than  the 
control performance of the VFD.   
Setting range: 0.00–3.00 
0: Display according to the motor type: only the 
parameters  corresponding  to  the  current  motor 
type  are  displayed  for  the  convenient  for  the 
customers in this mode.   
1:  All  parameters  are  displayed:  all  parameters 
are displayed in this mode.