Goodrive300 Series VFD    Function parameters 
63 
Detailed instruction of parameters 
4: HDI 
5: Modbus communication 
6: PROFIBUS\CANopen communication 
7: Ethernet communication   
8: Reserved 
Note:  For  setting  modes  of  1–9,  100% 
corresponds to three times of the motor current. 
Keypad 
setting of 
electromotion 
torque   
The function code is used to set the  limit of the 
torque. 
Setting range: 0.0–300.0% (motor rated current) 
Keypad 
setting of 
braking   
torque 
Weakening 
coefficient in 
constant 
power zone   
The usage of motor in weakening control.   
Flux-weakening 
coefficient of the motor
T
0.1
1.0
2.0
Minimum flux-weakening limit
 
Function code P03.22 and P03.23 are effective at 
constant  power.  The  motor  will  enter  into  the 
weakening  state  when  the  motor  runs  at  rated 
speed.  Change  the  weakening  curve  by 
modifying the weakening control coefficienct. The 
bigger the  weakening control  coefficienct  is,  the 
steeper the weak curve is. 
Setting range of P03.22: 0.1–2.0 
Setting range of P03.23: 10%–100% 
Lowest 
weakening 
point in 
constant 
power zone 
P03.24 set the Max. Voltage of the VFD, which is 
dependent on the site situation. 
Setting range: 0.0–120.0% 
Preactivate  the  motor  when  the  VFD  starts  up.