Goodrive300 Series VFD Function parameters
72
Detailed instruction of parameters
communication, and the communication address
is 0x200A.
Terminals
control
running mode
Set the control operation mode of the terminals.
0: 2-wire control 1; the enabling function and
direction determination function are integrated.
This mode is widely used. It determines the
rotation direction by the defined FWD and REV
terminals command.
FWD
REV
COM
K1
K2
Running
command
FWD REV
OFF OFF
OFF
OFF
ON
ON
ON ON
Stop
Holding on
Forward
running
Reverse
running
1: 2-wire control 2; the enabling function and the
direction determination function are separated. In
this mode, FWD is the enablingterminal, and the
direction depends on the state of the defined
REV.
FWD
REV
COM
K1
K2
Running
command
FWD REV
OFF OFF
OFF
OFF
ON
ON
ON ON
Stop
Stop
Forward
running
Reverse
running
2: 3-wire control 1; in this mode, SIn is the
enabling terminal, and the running command is
generated by FWD and the direction is controlled
by REV. SIn must be in the closed state when the
VFD is running. The FWD terminal generates a
rising edge signal, and the VFD starts to run. The
status of the REV terminal determines the running
direction. When the VFD stops, the SIn terminal
needs to be disconnected to complete the
stopping.