Goodrive300 Series VFD Function parameters
74
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
Sln
FWD
REV
Direction
ON
OFF→ON
ON
Forward
OFF
Reverse
ON
ON
OFF→ON
Forward
OFF
Reverse
ON→OFF
Decelerate
to stop
SIn: 3-wire operation control; FWD: Forward
running; REV: Reverse running
Note: For the 2-wire running mode, when the
FWD/REV terminal is valid, and the VFD stops
because of the stop command from other
sources, the VFD won't work when the stopping
command is canceled even the control terminal
FWD/REV is still valid;. Only when FWD/REV is
re-triggered, the VFD can start again. For
example, the PLC single-cycle stop command,
fixed-period stop command, and the STOP/RST
stop command that is valid in terminal control
mode (see P07.04).
P05.14
Switch-on
delay of S1
terminal
The function code defines the corresponding
delay time of electrical level of the programmable
terminals during switching on and switching off.
Si electrical level
Si valid
Invalid Invalid
Switcn-on
delay
Switcn-off
delay
Valid
Setting range: 0.00050.000s
0.000s
P05.15
Switch-off
delay of S1
terminal
0.000s
P05.16
Switch-on
delay of S2
terminal
0.000s
P05.17
Switch-off
delay of S2
terminal
0.000s
P05.18
Switch-on
delay of S3
terminal
0.000s