Goodrive300 Series VFD Function parameters
83
Detailed instruction of parameters
to clear the set value of UP/DOWN.
5: Coast to stop. Press QUICK/JOG to coast to
stop.
6: Shift the given manner of running commands.
Press QUICK/JOG to shift the given manner of
running commands.
7: Quick commission mode (committee according
to the non-factory parameter)
Note: Press QUICK/JOG to shift between
forward rotation and reverse rotation, the VFD
does not remember the state after shifting during
powering off. The VFD will run in the running
direction set according to parameter P00.13
during next powering on.
Shifting
sequence
selection of
QUICK/JOG
commands
When P07.02=6, set the shifting sequence of
running command channels.
0: Keypad control→terminals
control→communication control
1: Keypad control←→terminals control
2: Keypad control←→communication control
3: Terminals control←→communication control
STOP/RST is valid for stop function. STOP/RST
is valid in any state for the fault reset.
0: Only valid for the keypad control
1: Both valid for keypad and terminals control
2: Both valid for keypad and communication
control
3: Valid for all control modes
0x0000–0xFFFF
BIT0: running frequency (Hz on)
BIT1: set frequency (Hz flickering)
BIT2: bus voltage (Hz on)
BIT3: output voltage (V on)
BIT4: output current (A on)
BIT5: running rotation speed (rpm on)
BIT6: output power (% on)
BIT7: output torque (% on)
BIT8: PID reference (% flickering)