Goodrive300 Series VFD Function parameters
102
Detailed instruction of parameters
P10 Group Simple PLC and multi-step speed control
0: Stop after running once. The VFD has to be
commanded again after finishing a cycle.
1: Run at the final value after running once. After
finish a signal, the VFD will keep the running
frequency and direction of the last run.
2: Cycle running. The VFD will keep on running
until receiving a stop command d. And then, the
system will stop.
0: Power loss without memory
1: Power loss with memory; PLC record the
running stage and frequency when power loss.
The frequency setting range of stage 0–15:
-100.0–100.0%,100.0% of the frequency setting
corresponds to the Max. Frequency P00.03.
The operation time setting of stage 0–15: the time
unit is determined by P10.37. When selecting
simple PLC running, set P10.02–P10.33 to define
the running frequency and time of all stages.
Note: The symbol of multi-step determines the
running direction of simple PLC. The negative
value means reverse rotation.
P10.02
P10.04
P10.06
P10.32
P10.30
P10.28DEC time
(2 stages)
ACC time
(2 stags)
P10.03 P10.05 P10.07 P10.31 P10.33
If multi-step speed operation is selected,
multi-step speeds are in the range of --f
max
–f
max
and it can be set continuously.
Goodrive300 series VFDs can set 16 stages
speed, selected by the combination of multi-step