Goodrive350 series high-performance multi-function inverter  Chapter 6 
-127- 
Detailed parameter description 
Running 
protection of 
power-on 
terminal 
When the running command channel is controlled by 
terminals, the system will detect running terminal 
state automatically during power up. 
0: Terminal running command is invalid during power 
up. The inverter will not run during power up even if 
the running command terminal is detected to be 
valid, and the system is in running protection state. 
The inverter will run only after this terminal is 
cancelled and enabled again. 
1: Terminal running command is valid during power 
up. The system will start the inverter automatically 
after initialization is done if the running command 
terminal is detected to be valid during power up. 
Note: This function must be set with caution, 
otherwise, serious consequences may occur. 
Action selection 
when the running 
frequency is 
below lower limit 
(lower limit 
should be larger 
than 0)   
This function code is used to set the running state of 
inverter when the set frequency is below lower limit 
frequency. 
0: Run in lower limit of the frequency 
1: Stop 
2: Sleep 
When the set frequency is below lower limit 
frequency, the inverter coasts to stop; when the set 
frequency is above lower limit again and continues to 
be so after the time set by P01.20 elapses, the 
inverter will be restored to running state 
automatically. 
This function code is used to set the sleep delay. 
When the running frequency of inverter is below the 
lower limit frequency, the inverter enters sleep state; 
when the set frequency is above the lower limit again 
and continues to be so after the time set by P01.20 
elapses, the inverter will run automatically.