Goodrive350 series high-performance multi-function inverter  Chapter 6 
-128- 
Detailed parameter description 
RunSleep
t1 t2
Run
Time t
Output frequency f
t3=P01.20
t1<t2, the inverter does not run
t1+t2=t3, the inverter runs
t3
 
Setting range: 0.0–3600.0s (valid when P.01.19 is 2)   
This function code sets the automatic running of the 
inverter at next power-on after power down. 
0: Disabled restart 
1: Enable restart, namely the inverter will run 
automatically after the time set by P01.22 elapses if 
the starting conditions are met. 
Waiting time of 
restart after 
power cut 
This function code sets the waiting time before 
automatically running at next power-on after power 
down. 
Output frequency 
Running  
Power off 
Power on
 
Running
 
t
t1 t2
t1=P01.22
t2=P01.23
 
Setting range: 0.0–3600.0s (valid when P01.21 is 1) 
This function code sets the delay of the inverter’s 
wake-up-from-sleep after running command is given, 
the inverter will start to run and output after the time 
set by P01.23 elapses to realize brake release. 
Setting range: 0.0–600.0s 
Open-loop 0Hz 
output selection 
0: No voltage output 
1: With voltage output 
2: Output as per DC brake current of stop 
Deceleration time 
of 
emergency-stop 
Time of starting 
section of 
deceleration S 
curve