EasyManua.ls Logo

INVT Goodrive GD35-004G-4-H1

INVT Goodrive GD35-004G-4-H1
298 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Goodrive35 Series Closed-loop Vector Control VFD Function parameters
100
Functio
n code
Name
Detailed instruction of parameters
Default
value
Modif
y
PID adjustment is different from the current running
direction, operate the close-loop adjustment output
that is opposite to current running direction..
LED hundreds: P00.08 is 0
0: Limit to the maximum frequency
1: Limit to frequency A
P09.14
PID deviation limit
0.0200.0%
200.0%
P09.15
PID command of
ACC/DEC time
0.01000.0s
0.0 s
P09.16
PID output filter time
0.00010.000s
0.000 s
P09.17
PID pre-setting
-100.0100.0%
0.0%
P10 Group Simple PLC and multi-step speed control
P10.00
Simple PLC
0: Stop after running once. The VFD has to be
commanded again after finishing a cycle.
1: Run at the final value after running once. After
finish a signal, the VFD will keep the running
frequency and direction of the last run.
2: Cycle running. The VFD keeps running until
receiving a stop command, then system will stop.
0
P10.01
Simple PLC
memory
0: Power loss without memory
1: Power loss with memory; PLC record the running
stage and frequency when power loss.
0
P10.02
Multi-step speed 0
The frequency setting range of stage 015:
-100.0100.0%, 100.0% of the frequency setting
corresponds to max. output frequency P00.03.
The operation time setting of stage 015: the time
unit is determined by P10.37..
When selecting simple PLC running, set
P10.02P10.33 to define the running frequency and
time of all stages.
Note: The symbol of multi-step determines the
running direction of simple PLC. The negative value
means reverse rotation.
0.0%
P10.03
Running time of step
0
0.0 s
P10.04
Multi-step speed 1
0.0%
P10.05
The running time of
step 1
0.0 s
P10.06
Multi-step speed 2
0.0%
P10.07
The running time of
step 2
0.0 s
P10.08
Multi-step speed 3
0.0%
P10.09
The running time of
step 3
0.0 s
P10.10
Multi-step speed 4
0.0%
P10.11
The running time of
0.0 s

Table of Contents

Related product manuals