The  parameters  of  P03.00–P03.05  are  applicable 
only to the vector control mode. When the frequency 
is  lower  than  P03.02  (Low-point  frequency  for 
switching), the ASR PI parameters are P03.00 and 
P03.01. When the frequency  is higher  than  P03.05 
(High-point  frequency  for  switching),  the  ASR  PI 
parameters  are  P03.03  and  P03.04.  When  the 
frequency  is  between  P03.02  and  P03.05,  the  PI 
parameters are obtained based on the linear change 
of these two groups of parameters, as shown in the 
following figure. 
 
You can adjust the dynamic response characteristics 
of  the  automatic  speed  regulator  (ASR)  in  vector 
control  by  setting  the  ASR  proportional  gain  and 
integral time.  Both  increasing  the  proportional gain 
and decreasing the integral time can accelerate the 
dynamic  response  of  the  ASR.  However,  if  the 
proportional gain is too large  or the integral time is 
too short, system oscillation or overadjustment may 
be  caused.  If  the  proportional  gain  is  too  small, 
system  steady-state  oscillation  may  be  easily 
caused, and static speed error may also occur. 
The  ASR  PI  parameters  are  closely  related  to  the 
inertia  of  the  system.  The  default  PI  parameters 
need to be modified based on the characteristics of 
loads to meet requirements of various scenarios. 
The setting range of P03.00: 0.0–200.0 
The setting range of P03.01: 0.000–10.000s 
The setting range of P03.02: 0.00 Hz–P03.05 
The setting range of P03.03: 0.0–200.0