Goodrive35 Series Closed-loop Vector Control VFD Basic operation instruction
159
Function
code
Name
Detailed instruction of parameters
Default
value
P01.18
Terminal
running protection when
powering on
0: The terminal running command is
invalid when powering on
1: The terminal running command is
valid when powering on
0
P01.19
Action if running frequency<
lower limit frequency (valid >0)
0: Run at the lower-limit frequency
1: Stop
2: Hibernation
3: Run at zero frequency
0
P01.20
Hibernation restore delay time
0.03600.0s (valid when P01.19=2)
0.0s
P01.21
Restart after power off
0: Disable
1: Enable
0
P01.22
The waiting time of restart after
power off
0.03600.0 s (valid when P01.21=1)
1.0s
P01.23
Start delay time
0.0060.00 s
0.00s
P01.24
Delay time of the stopping speed
0.0060.00 s
0.00s
P05.01P
05.09
Digital input function selection
1: Forward rotation operation
2: Reverse rotation operation
4: Forward rotation jogging
5: Reverse rotation jogging
6: Coast to stop
7: Fault reset
8: Operation pause
21: ACC/DEC time option 1
22: ACC/DEC time option 2
30: ACC/DEC prohibition
P08.00
ACC time 2
0.03600.0 s
Depend on
model
P08.01
DEC time 2
0.03600.0 s
Depend on
model
P08.02
ACC time 3
0.03600.0 s
Depend on
model
P08.03
DEC time 3
0.03600.0 s
Depend on
model
P08.04
ACC time 4
0.03600.0 s
Depend on
model
P08.05
DEC time 4
0.03600.0 s
Depend on
model