Goodrive100-PV Series Solar Pumping VFD Function parameters
31
Function
code
Name
Detailed illustration of parameters
Default
Modify
Output voltage
Output
frequency
Cut-off
boost
b
Setting range of P04.01: 0.0%:
(automatic) 0.1%10.0%
Setting range of P04.02: 0.0%50.0%
P04.03
V/F frequency
point 1 of motor 1
If P04.00 =1, the user can set V//F curve
by P04.03P04.08.
V/F is set to the motor load.
Note: V1 V2V3; f1 f2 f3. If the
low-frequency voltage is high,
overtemperature and burning may occur
and the overcurrent stall and protection
may occur to the VFD.
Output voltage
Output
frequency
(Hz)
V1
V2
V3
f1 f2 f3
100.0%
b
f
b
Setting range of P04.03: 0.00HzP04.05
Setting range of P04.04: 0.0%110.0%
(rated voltage of motor1)
Setting range of P04.05: P04.03P04.07
Setting range of P04.06: 0.0%110.0%
(rated voltage of motor1)
Setting range of P04.07: P04.05P02.02
0.00Hz
P04.04
V/F voltage point
1 of motor 1
00.0%
P04.05
V/F frequency
point 2 of motor 1
00.00
Hz
P04.06
V/F voltage point
2 of motor 1
00.0%
P04.07
V/F frequency
point 3 of motor 1
00.00
Hz
P04.08
V/F voltage point
3 of motor 1
00.0%